Below are explanations for each possible error message on the TAP II or TAP II Pro Controllers – as well as possible causes and troubleshooting steps…
TAP Kiln Controller Table of Errors
| Message on Controller | Error Condition | Possible Cause | Possible Solution |
|---|---|---|---|
| The maximum allowable temperature for this device has been exceeded, the firing is Aborted. | Max Temperature Exceeded | Programmed Temperature Too High Relay Failure | Reduce programmed top temperature Verify relay turns off when 12VDC removed |
| The controller has detected a failure to heat, the firing is Aborted. | Failing to Heat for Too Long | Intermittent/Shorted Thermocouple Relay Failure Element Failure Reduced Power Available | Check thermocouple to ensure not broken or shorted Verify relay turns off when 12VDC removed Verify element is not open circuit Verify source power |
| The controller has detected a ramp rate in excess of the programmed ramp rate, the firing is aborted. This could be due to a latched relay. | Ramp Rate Exceeded | Relay Failure Controller Output Failure | Verify relay turns off when 12VDC removed Verify controller output 0VDC when in standby |
| The controller has detected a failure to cool. This firing is aborted. | Failure to Cool | Relay Failure Controller Output Failure | Verify relay turns off when 12VDC removed Verify controller output 0VDC when in standby |
| The controller has detected a high deviation from the setpoint, the firing is aborted. This could be due to a latched relay. | High Temp Deviation From Setpoint | Relay Failure Controller Output Failure | Verify relay turns off when 12VDC removed Verify controller output 0VDC when in standby |
| The controller has detected a rising temperature while not actively firing. This could be the result of latched relays. | Rising Temperature Alarm | Relay Failure Controller Output Failure | Verify relay turns off when 12VDC removed Verify controller output 0VDC when in standby |
| No thermocouple is detected. Firing is Aborted. | No Thermocouple Detected Alarm | Thermocouple Failure Thermocouple Connection Bad Controller Input Failure | Verify thermocouple is not broken Verify thermocouple connection at the controller and isothermal block Contact SDS Industries |
Failed to initialize AD7799 Hardware. | Analog to Digital Converter Has Failed | Analog to Digital Converter Has Failed | Contact SDS Industries as a replacement controller will be needed |
Please contact our Support Team with any questions. We’re happy to assist you! You can find more detailed troubleshooting steps here.
i received an error message error notification what does it mean if my controller says max temp notification failure to heat firing aborted failure to cool temperature deviation no thermocouple how do i troubleshoot what do i do my controller is saying how to fix how to resolve kiln shut off firing stopped temperature on my kiln error alerts errors